Search

M-Bus 60 v.4800

Monitoring the M-Bus transmission line via RS232 connector from PLC or PC. It has an additional input of M-Bus SLAVE signal, enabling operation in repeater mode – M-Bus line amplifier.

964,25  (net)
1186,03  (gross)

Product fit

Telemetry of energy utilities

A modern surveillance system

Instrumentation and Electrical Engineering

Product description

Monitoring the M-Bus transmission line via RS232 connector from PLC or PC. Includes an additional input of M-Bus SLAVE signal, enabling operation in repeater mode – M-Bus line amplifier. Three speed versions optimized accordingly for long, medium, and short transmission lines.

Technical data:

  • Power supply 20 ÷ 35 VDC, 20 ÷ 24 VAC
  • Current consumption 0.1 A ÷ 0.5 A / 24 VDC
  • Maximum number of unit loads (standard M-Bus receivers) 60
  • M-Bus line supply current – in the absence of transmission 90 mA max
  • Short-term M-Bus supply current 140 mA
  • Voltage at M-Bus terminals – in the absence of transmission 36 V
  • MBUS transient voltage suppressor TRANSIL 43V 600W/1ms
  • RS232 transmission drawer-type connector BH10

Transmission speed:

  • for M-Bus 60 version – 4800 up to 4800 baud – for long lines
  • for M-Bus 60 version – 9600 up to 9600 baud – for medium lines
  • for M-Bus 60 version – 19200 up to 19200 baud – for short lines
  • Normative reference conditions CEN/TC 176 WG 4
  • M-Bus – converter power supply 100 V AC/DC
  • M-Bus – RS 232 connector (MBUS SLAVE) 100 V AC/DC
  • Converter power supply – RS232 connector (MBUS SLAVE) 100 V AC/DC
  • BH 10 (RS232) pin 2 connector output – TxD (to RxD of the computer)
  • pin 3 – RxD (from TxD of the computer)
  • pin 5